Cooling [Ceiling Cassette (4-Way Flow Type)]; Cooling Capacity With Puhy,Pury-Rp200-250Yjm - Mitsubishi Electric PUHY-RP-Y(S)JM-B Data Book

Table of Contents

Advertisement

5. Cooling [Ceiling cassette (4-way flow type)]

5-1. Cooling capacity with PUHY,PURY-RP200-250YJM

5. Cooling [Ceiling cassette (4-way flow type)]
PLFY-P-VCM-E
Model
Outdoor
size
air temp.
21.5°C D.B.
(Rated kW)
15°C W.B.
°C D.B.
CA
20.0
2.1
22.5
2.1
25.0
2.1
27.5
2.1
30.0
2.0
20
(2.2)
32.5
2.0
35.0
2.0
37.5
1.9
40.0
1.9
43.0
1.8
20.0
2.7
22.5
2.7
25.0
2.7
27.5
2.7
30.0
2.6
25
(2.8)
32.5
2.6
35.0
2.5
37.5
2.5
40.0
2.4
43.0
2.4
20.0
3.4
22.5
3.4
25.0
3.4
27.5
3.4
30.0
3.3
32
(3.6)
32.5
3.3
35.0
3.2
37.5
3.2
40.0
3.1
43.0
3.0
20.0
4.3
22.5
4.3
25.0
4.3
27.5
4.3
30.0
4.2
40
(4.5)
32.5
4.1
35.0
4.0
37.5
4.0
40.0
3.9
43.0
3.8
23°C D.B.
25°C D.B.
16°C W.B.
18°C W.B.
SHC
CA
SHC
CA
1.8
2.2
1.8
2.3
1.8
2.2
1.8
2.3
1.8
2.2
1.8
2.3
1.8
2.1
1.8
2.3
1.8
2.1
1.8
2.2
1.7
2.1
1.8
2.2
1.7
2.0
1.8
2.1
1.7
2.0
1.8
2.1
1.7
2.0
1.8
2.1
1.7
1.9
1.7
2.0
2.1
2.8
2.2
2.9
2.1
2.8
2.2
2.9
2.1
2.8
2.2
2.9
2.1
2.7
2.2
2.9
2.1
2.7
2.2
2.8
2.1
2.6
2.2
2.8
2.1
2.6
2.1
2.7
2.0
2.5
2.1
2.7
2.0
2.5
2.1
2.6
2.0
2.4
2.1
2.6
2.6
3.5
2.7
3.8
2.6
3.5
2.7
3.8
2.6
3.5
2.7
3.8
2.6
3.5
2.7
3.7
2.6
3.4
2.6
3.6
2.5
3.4
2.6
3.6
2.5
3.3
2.6
3.5
2.5
3.3
2.6
3.4
2.4
3.2
2.5
3.4
2.4
3.1
2.5
3.3
3.0
4.4
3.1
4.7
3.0
4.4
3.1
4.7
3.0
4.4
3.1
4.7
3.0
4.4
3.1
4.6
3.0
4.3
3.1
4.6
3.0
4.2
3.0
4.5
2.9
4.1
3.0
4.4
2.9
4.1
3.0
4.3
2.8
4.0
2.9
4.2
2.8
3.9
2.9
4.1
INDOOR UNITS
Indoor air temp.
27°C D.B.
28°C D.B.
19°C W.B.
20°C W.B.
SHC
CA
SHC
CA
1.8
2.4
2.0
2.5
1.8
2.4
2.0
2.5
1.8
2.4
2.0
2.4
1.8
2.3
1.9
2.4
1.8
2.3
1.9
2.3
1.8
2.2
1.9
2.3
1.8
2.2
1.9
2.3
1.7
2.2
1.9
2.2
1.7
2.1
1.9
2.2
1.7
2.1
1.8
2.1
2.2
3.0
2.3
3.1
2.2
3.0
2.3
3.1
2.2
3.0
2.3
3.1
2.2
3.0
2.3
3.0
2.2
2.9
2.3
3.0
2.1
2.9
2.3
2.9
2.1
2.8
2.3
2.9
2.1
2.8
2.2
2.8
2.1
2.7
2.2
2.8
2.0
2.6
2.2
2.7
2.7
3.9
2.8
4.0
2.7
3.9
2.8
4.0
2.7
3.9
2.8
4.0
2.6
3.8
2.8
3.9
2.6
3.7
2.8
3.8
2.6
3.7
2.7
3.8
2.6
3.6
2.7
3.7
2.5
3.5
2.7
3.6
2.5
3.5
2.7
3.6
2.5
3.4
2.6
3.5
3.1
4.9
3.3
5.0
3.1
4.9
3.3
5.0
3.1
4.9
3.3
5.0
3.1
4.8
3.2
4.9
3.0
4.7
3.2
4.8
3.0
4.6
3.2
4.7
3.0
4.5
3.1
4.6
2.9
4.4
3.1
4.5
2.9
4.3
3.0
4.4
2.8
4.2
3.0
4.3
CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
30°C D.B.
32°C D.B.
22°C W.B.
24°C W.B.
SHC
CA
SHC
CA
2.0
2.6
1.9
2.8
2.0
2.6
1.9
2.8
1.9
2.6
1.9
2.7
1.9
2.5
1.9
2.7
1.9
2.5
1.9
2.6
1.9
2.4
1.9
2.6
1.9
2.4
1.8
2.5
1.9
2.3
1.8
2.5
1.8
2.3
1.8
2.4
1.8
2.2
1.8
2.3
2.3
3.3
2.3
3.5
2.3
3.3
2.3
3.5
2.3
3.3
2.3
3.5
2.3
3.2
2.3
3.4
2.3
3.2
2.2
3.3
2.3
3.1
2.2
3.3
2.2
3.0
2.2
3.2
2.2
3.0
2.2
3.1
2.2
2.9
2.2
3.1
2.2
2.8
2.1
3.0
2.8
4.3
2.8
4.6
2.8
4.3
2.8
4.6
2.8
4.2
2.8
4.5
2.8
4.1
2.7
4.4
2.7
4.1
2.7
4.3
2.7
4.0
2.7
4.2
2.7
3.9
2.6
4.1
2.7
3.8
2.6
4.0
2.6
3.7
2.6
3.9
2.6
3.6
2.5
3.8
3.3
5.3
3.2
5.7
3.3
5.3
3.2
5.7
3.2
5.3
3.2
5.6
3.2
5.2
3.2
5.5
3.2
5.1
3.1
5.4
3.1
5.0
3.1
5.3
3.1
4.9
3.0
5.2
3.1
4.8
3.0
5.0
3.0
4.7
3.0
4.9
3.0
4.5
2.9
4.8
kcal/h=kW x 860 , BTU/h = kW x 3,412
SHC
1.9
1.9
1.9
1.9
1.9
1.8
1.8
1.8
1.8
1.8
2.3
2.3
2.3
2.2
2.2
2.2
2.2
2.1
2.1
2.1
2.8
2.8
2.7
2.7
2.7
2.6
2.6
2.6
2.5
2.5
3.2
3.2
3.2
3.1
3.1
3.0
3.0
2.9
2.9
2.9
134