Mitsubishi Electric PUHY-RP-Y(S)JM-B Data Book page 213

Table of Contents

Advertisement

2. M-NET control
2-4-2. Rule of setting address
Unit
Indoor unit
Outdoor unit
BC controller
(Main)
BC controller
(Sub)
ME, LOSSNAY
Remote controller
(Main)
ME, LOSSNAY
Remote controller
(Sub)
Group remote
controller
System remote
controller
ON/OFF remote
controller
AG-150A
GB-50ADA
AT-50A
PAC-YG50ECA
BAC-HD150
LMAP02-E
Note1: To set the address to "100", set it to "50"
Note2: Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected.
OC, OS1 and OS2 are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending
order of their address.
Address setting
Example
01 ~ 50
10
51 ~ 99, 100
(Note1)
10
52 ~ 99, 100
10
52 ~ 99, 100
10
1
101 ~ 150
Fixed
10
1
151 ~ 199, 200
Fixed
10
2
201 ~ 250
Fixed
10
000, 201 ~ 250
100
10
000, 201 ~ 250
100
10
0,2
0~5
000, 201 ~ 250
100
10
0,2
0~5
000, 201 ~ 250
100
10
0,2
0~5
000, 201 ~ 250
100
10
2
201 ~ 250
Fixed
10
SYSTEM DESIGN
Use the most recent address within the same group of
indoor units. Make the indoor units address connected
to the BC controller (Sub) larger than the indoor units
address connected to the BC controller (Main).
If applicable, set the sub BC controllers in an PURY
system in the following order:
(1) Indoor unit to be connected to the BC controller (Main)
1
(2) Indoor unit to be connected to the BC controller (No.1 Sub)
(3) Indoor unit to be connected to the BC controller (No.2 Sub)
Set the address so that (1)<(2)<(3)
The smallest address of indoor unit in same refrigerant
system + 50
Assign sequential address numbers to the outdoor
units in one refrigerant circuit system. OC, OS1 and
OS2 are automatically detected. (Note 2)
1
Please reset one of them to an address between 51
and 99 when two addresses overlap.
The address automatically becomes "100" if it is set
as "01~ 50"
The address of outdoor unit + 1
Please reset one of them to an address between 51
and 99 when two addresses overlap.
The address automatically becomes "100" if it is set
1
as "01~ 50"
Lowest address within the indoor units connected to
the BC controller (Sub) plus 50.
1
The smallest address of indoor unit in the group + 100
The place of "100" is fixed to "1"
1
The address of main remote controller + 50
The address automatically becomes "200" if it is set
as "00"
1
The smallest group No. to be managed + 200
1
1
The smallest group No. to be managed + 200
The smallest group No. to be managed is changeable.
1
0~9
1
0~9
Settings are made on the initial screen of AG-150A.
1
0~9
Settings are made with setting tool of BM ADAPTER.
1
1
Note
210