6. CAPACITY TABLES
6-3-2. Heating capacity correction
PUHY-RP200, 250YJM-B(-BS)
1.00
0.95
0.90
0
20
40
60
Piping equivalent length (m)
PUHY-RP300, 350YJM-B(-BS)
1.00
0.95
0.90
0
20
40
60
Piping equivalent length (m)
PUHY-RP400, 450, 500, 550YSJM-B(-BS)
1.00
0.95
0.90
0
20
40
60
Piping equivalent length (m)
6-3-3. How to obtain the equivalent piping length
1. PUHY-RP200YJM-B(-BS)
Equivalent length = (Actual piping length to the farthest indoor unit ) + (0.35 x number of bent on the piping) [m]
2. PUHY-RP250, 300YJM-B(-BS)
Equivalent length = (Actual piping length to the farthest indoor unit ) + (0.42 x number of bent on the piping) [m]
3. PUHY-RP350YJM-B(-BS)
Equivalent length = (Actual piping length to the farthest indoor unit ) + (0.47 x number of bent on the piping) [m]
4. PUHY-RP400, 450, 500, 550, 600, 650YSJM-B(-BS)
Equivalent length = (Actual piping length to the farthest indoor unit ) + (0.50 x number of bent on the piping) [m]
5. PUHY-RP700, 750, 800YSJM-B(-BS)
Equivalent length = (Actual piping length to the farthest indoor unit ) + (0.70 x number of bent on the piping) [m]
6. PUHY-RP850, 900YSJM-B(-BS)
Equivalent length = (Actual piping length to the farthest indoor unit ) + (0.80 x number of bent on the piping) [m]
80
100
120
140
80
100
120
140
80
100
120
140
OUTDOOR UNITS
PUHY-RP600, 650YSJM-B(-BS)
1.00
0.95
0.90
0
20
40
Piping equivalent length (m)
PUHY-RP700, 750, 800YSJM-B(-BS)
1.00
0.95
0.90
0
20
40
Piping equivalent length (m)
PUHY-RP850, 900YSJM-B(-BS)
1.00
0.95
0.90
0
20
40
Piping equivalent length (m)
60
80
100
120
60
80
100
120
60
80
100
120
45