Mitsubishi Electric PUHY-RP-Y(S)JM-B Data Book page 197

Table of Contents

Advertisement

1. Electrical work
PFFY-P-VLRM-E
PFFY-P20VLRM-E
PFFY-P25VLRM-E
PFFY-P32VLRM-E
PFFY-P40VLRM-E
PFFY-P50VLRM-E
PFFY-P63VLRM-E
PFFY-P-VLRMM-E
PFFY-P20VLRMM-E
PFFY-P25VLRMM-E
PFFY-P32VLRMM-E
PFFY-P40VLRMM-E
PFFY-P50VLRMM-E
PFFY-P63VLRMM-E
GUF-RDH3
GUF-50RD(H)3
GUF-100RD(H)3
Power supply
Volts / Hz
Range +-10%
220-240V / 50Hz
Max.: 264V
208-230V / 60Hz
Min.: 187V
Power supply
Volts / Hz
Range +-10%
Max.: 264V
220-240V / 50Hz
Min.: 198V
Power supply
Volts / Hz
Range +-10%
220-240V / 50Hz
Max.: 264V
220V / 60Hz
Min.: 198V
SYSTEM DESIGN
Symbols: MCA : Max.Circuit Amps (=1.25xFLA) FLA : Full Load Amps
IFM :Indoor Fan Motor
MCA(A) (50 / 60Hz)
0.24 / 0.31
0.24 / 0.31
0.36 / 0.38
0.40 / 0.41
0.50 / 0.51
0.58 / 0.59
MCA(A) (50 / 60Hz)
0.59 / 0.58
0.59 / 0.58
0.69 / 0.69
0.78 / 0.76
0.80 / 0.79
0.93 / 0.93
MCA(A) (50 / 60Hz)
1.85 / 1.85
3.49 / 3.49
Output : Fan motor rated output
IFM
Output(kW)
FLA(A) (50 / 60Hz)
0.015
0.19 / 0.25
0.015
0.19 / 0.25
0.018
0.29 / 0.30
0.030
0.32 / 0.33
0.035
0.40 / 0.41
0.050
0.46 / 0.47
IFM
Output(kW)
FLA(A) (50 / 60Hz)
0.096
0.47 / 0.46
0.096
0.47 / 0.46
0.096
0.55 / 0.55
0.096
0.62 / 0.61
0.096
0.64 / 0.63
0.096
0.74 / 0.74
IFM
Output(kW)
FLA(A) (50 / 60Hz)
0.081x2
1.48 / 1.48
0.16x2
2.79 / 2.79
194

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pury-rp-yjm-b

Table of Contents