4. Cooling [Ceiling cassette (2-way flow type)]
PLFY-P-VLMD-E
Model
Outdoor
size
air temp.
21.5°C D.B.
(Rated kW)
15°C W.B.
°C D.B.
CA
20.0
10.6
22.5
10.6
25.0
10.6
27.5
10.6
30.0
10.4
100
(11.2)
32.5
10.2
35.0
10.0
37.5
9.8
40.0
9.6
43.0
9.4
20.0
13.3
22.5
13.3
25.0
13.3
27.5
13.3
125
30.0
13.0
(14.0)
32.5
12.8
35.0
12.5
37.5
12.3
40.0
12.1
43.0
11.8
23°C D.B.
25°C D.B.
16°C W.B.
18°C W.B.
SHC
CA
SHC
CA
7.7
11.0
7.9
11.8
7.7
11.0
7.9
11.8
7.7
11.0
7.9
11.8
7.7
10.9
7.9
11.6
7.6
10.7
7.8
11.3
7.5
10.5
7.7
11.1
7.4
10.3
7.6
10.9
7.3
10.1
7.5
10.7
7.2
9.9
7.4
10.5
7.1
9.7
7.3
10.2
9.8
13.8
10.1
14.7
9.8
13.8
10.1
14.7
9.8
13.8
10.1
14.7
9.7
13.6
10.0
14.4
9.6
13.4
9.9
14.2
9.5
13.2
9.8
13.9
9.4
12.9
9.6
13.7
9.3
12.7
9.5
13.4
9.1
12.4
9.4
13.1
9.0
12.1
9.3
12.8
INDOOR UNITS
Indoor air temp.
27°C D.B.
28°C D.B.
19°C W.B.
20°C W.B.
SHC
CA
SHC
CA
7.9
12.1
8.3
12.5
7.9
12.1
8.3
12.5
7.9
12.1
8.3
12.4
7.8
11.9
8.2
12.2
7.7
11.6
8.1
12.0
7.6
11.4
8.0
11.7
7.5
11.2
7.9
11.5
7.4
11.0
7.8
11.3
7.3
10.8
7.7
11.1
7.2
10.5
7.6
10.8
10.0
15.2
10.6
15.6
10.0
15.2
10.6
15.6
10.0
15.1
10.5
15.5
9.9
14.8
10.4
15.2
9.8
14.6
10.3
14.9
9.6
14.3
10.2
14.7
9.5
14.0
10.1
14.4
9.4
13.8
9.9
14.1
9.3
13.5
9.8
13.8
9.1
13.2
9.7
13.5
CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
30°C D.B.
32°C D.B.
22°C W.B.
24°C W.B.
SHC
CA
SHC
CA
8.2
13.2
8.1
14.2
8.2
13.2
8.1
14.2
8.2
13.1
8.1
13.9
8.1
12.9
8.0
13.7
8.0
12.6
7.9
13.4
7.9
12.4
7.8
13.1
7.8
12.1
7.7
12.8
7.7
11.9
7.6
12.6
7.6
11.6
7.5
12.3
7.5
11.3
7.4
12.0
10.5
16.6
10.4
17.7
10.5
16.6
10.4
17.7
10.4
16.4
10.3
17.4
10.3
16.1
10.2
17.1
10.2
15.8
10.0
16.7
10.1
15.4
9.9
16.4
10.0
15.1
9.8
16.0
9.9
14.8
9.7
15.7
9.7
14.5
9.6
15.4
9.6
14.1
9.4
15.0
kcal/h=kW x 860 , BTU/h = kW x 3,412
SHC
8.0
8.0
8.0
7.9
7.8
7.7
7.6
7.5
7.4
7.2
10.2
10.2
10.1
10.0
9.9
9.8
9.7
9.5
9.4
9.3
125