11. M-NET CONTROL
11-3. System configuration restrictions
11-3-1. Common restrictions for the CITY MULTI system
For each Outdoor/Heat source unit, the maximum connectable quantity of Indoor unit is specified at its Specifications table.
A) 1 Group of Indoor units can have 1-16 Indoor units;
*OA processing unit GUF-RD(H) is considered as Indoor unit.
B) Maximum 2 remote controllers for 1 group;
*MA/ME remote controllers cannot be present together in 1group.
*When a PAR-CT01MA, PAR-4XMAA, or PAR-3XMAA ("X" represents 0 or later) is connected to a group, no other
MA remote controllers can be connected to the same group.
C) 1 Lossnay unit can interlock maximum 16 Indoor units; 1 Indoor unit can interlock only 1 Lossnay unit.
D) Maximum 3 System controllers are connectable when connecting to TB3 of the Outdoor/Heat source unit.
E) A maximum of 6 system controller are connectable to TB3 and TB7 of Outdoor/Heat source unit.
F) 4 System controllers or more are connectable when connecting to TB7 of the Outdoor/Heat source unit, if the
transmission power is supplied by the power supply unit PAC-SC51KUA.
*System controller connected as described in D) would have a risk that the failure of connected
Outdoor/Heat source unit would stop power supply to the System controller.
11-3-2. Ensuring proper communication power and the number of connected units for M-NET
In order to ensure proper communication among Outdoor/Heat source unit, Indoor unit, Lossnay, OA processing unit
GUF-RD(H), and Controllers, the transmission power situation for the M-NET should be observed. In some cases,
Transmission booster should be used. Taking the power consumption of Indoor unit as 1, the equivalent power consumption
or supply of others are listed at Table 1 and Table 2.
Both the transmission line for centralized controller and indoor-outdoor transmission line must meet the conditions listed
below. (Both conditions a) and b) must be met.)
a) [Total equivalent power consumption] ≤ [The equivalent power supply]
b) [Total equivalent number of units (Table 1)] ≤ [40]
Table 1 The equivalent power consumption and the equivalent number of units
Category
CITY MULTI indoor unit
OA unit
CITY MULTI connection kit
Air handling unit controller
CITY MULTI indoor unit *2
BC controller
PWFY *1
PFAV
PFV, PEV
MA remote controller/Lossnay
ME remote controller
System controller
ON/OFF controller
MN converter
Outdoor/Heat source unit
System control interface
A-M converter
*1 PWFY cannot be connected to PUMY model.
MEES19K116
Model
Except for the models indicated by *2
PEFY-AF2500, 3000, 4000, 5000, 6000MH
GUF-50, 100
PAC-LV11M-J
PAC-AH125, 140, 250, 500M-J
PDFY-P100VM-E-RE
CMB
P100VM-E-BU
P200VM-E1-AU
P200VM-E2-AU
(E)P100VM-E1-AU
(E)P100VM-E2-AU
P140VM-E1-AU
P140VM-E2-AU
P250, 300, 500, 600VM-E(-F)
P750, 900VM-E(-F)
P200, 250, 400, 500YM-A
PAR-CT01MA
PAR-21MA
PAR-31MA
PAR-32MA
PAR-33MA
PAR-40MA
PAC-YT52CRA
PAR-FA32MA
LGH
PZ-60DR-E
PZ-61DR-E
PZ-43SMF-E
PAR-U02MEDA
PZ-52SF
AE-200E
AE-50E
EW-50E
LM-AP
AG-150A
EB-50GU-J
PAC-IF01AHC-J
AT-50B
PAC-YG60MCA
PAC-YG66DCA
PAC-YG63MCA
PAC-YT40ANRA
CMS-MNG-E
TB7 power consumption
MAC-333IF-E
PAC-SF83MA-E
The equivalent power consumption
1
2
2
6
5
1
1
2
1
0
0.5
0.25
0
0.5
1.5
0.25
1
2
0
0
Y-Series
The equivalent number of units
1
2
1
1
1
1
1
2
1
0
1
1
0
1
5
1
1
1
0
0
47