Correction By Refrigerant Piping Length - Mitsubishi Electric PUHY-RP-Y(S)JM-B Data Book

Table of Contents

Advertisement

6. CAPACITY TABLES

6-3. Correction by refrigerant piping length

CITY MULTI system can extend the piping flexibly within its limitation for the actual situation. Yet, a decrease of cooling/heating
capacity could happen correspondently. Using following correction factor according to the equivalent length of the piping shown at
6-3-1 and 6-3-2, the capacity can be observed. 6-3-3 shows how to obtain the equivalent length of piping.
6-3-1. Cooling capacity correction
PURY-RP200YJM-B(-BS)
1
0.95
0.90
0.85
0.80
0.75
0.70
0.65
0
20
40
Piping equivalent length (m)
PURY-RP250YJM-B(-BS)
1
0.95
0.90
0.85
0.80
0.75
0.70
0.65
0
20
40
Piping equivalent length (m)
PURY-RP300YJM-B(-BS)
1
0.95
0.90
0.85
0.80
0.75
0.70
0.65
0
20
40
Piping equivalent length (m)
Total capacity of indoor unit
100
150
200
300
60
80
100
120
Total capacity of indoor unit
125
188
250
375
60
80
100
120
Total capacity of indoor unit
150
225
300
450
60
80
100
120
OUTDOOR UNITS
74