Mitsubishi Electric PUHY-RP-Y(S)JM-B Data Book page 267

Table of Contents

Advertisement

2. M-NET control
2-4-3-6. ME remote controller, Multi-refrigerant-system, System Controller at TB 7side, LOSSNAY, Booster for long M-NET wiring
PURY
OC
TB7
51
CN40
CN41
DipSW2-1
ON
TB3
BC controller
(Main)
52
TB02
TB2
Power supply unit
(PAC-SC51KUA)
*1
BC controller
92
TB02
000 or 201
SC
*1 System controller should connect to TB7 at Outdoor and use power supply unit together in Multi-Refrigerant-System.
For AG-150A, 24VDC should be used with the PAC-SC51KUA.
NOTE:
1. M-NET power is supplied by the Outdoor unit at TB3, while Indoor unit and ME RC consume the M-NET power for transmission
use. The power balance is needed to consider for long M-NET wiring. Details refer to 2-3 "System configuration restrictions".
2. Indoor units should be set with a branch number.
3. Assign an address to each of the sub BC controllers which equals the sum of the smallest address of the indoor
units that are connected to each sub BC controller and 50.
When the address assigned to sub BC controller overlaps those of any other units including outdoor units (OC/OS) or main BC controller,
sub BC controller will be given priority to have the address.
2-4-3-7. Example : BC, BC sub
PURY
OC
51
CN40
CN41
DipSW2-1
OFF
TB3
PURY
OC
TB7
91
CN40
CN41
DipSW2-1
ON
TB3
Group 1
Group 2
Indoor unit
01
02
TB5
TB5
101
102
ME R/C
ME R/C
Group 31
Group 32
Indoor unit
41
42
TB5
TB5
141
142
ME R/C
ME R/C
NOTE
• Indoor units should be set with a branch number.
• BC (main) address = O/U address + 1
• BC (sub) address = Lowest address within the indoor units connected to the BC controller (sub) + 50
• If applicable, set the sub BC controllers in an PURY system in the following order:
(1) Indoor unit to be connected to the BC controller (Main)
(2) Indoor unit to be connected to the BC controller (No.1 Sub)
(3) Indoor unit to be connected to the BC controller (No.2 Sub)
Set the address so that (1)<(2)<(3)
52
BC controllers
TB02
CMB-V-GA1(main)
01
02
TB5
TB5
TB5
101
Group 1
SYSTEM DESIGN
PURY
OC
TB7
97
CN40
CN41
DipSW2-1
ON
TB3
BC controller
(Sub)
03
80
TB5
TB2
TB02
Transmission Booster
PAC-SF46EPA
Group 33
Group 34
LOSSNAY
44
43
TB5
TB5
143
144
ME R/C
PZ-52SF-E
: M-NET wiring
54
BC controllers
TB02
CMB-V-GB1(No.1 sub)
03
04
05
TB5
TB5
104
Group 2
Group 21
30
TB3
TB5
130
180
ME R/C ME R/C
Group 35
Group 36
LOSSNAY
45
TB5
TB5
145
195
ME R/C ME R/C
: Piping
57
BC controllers
TB02
CMB-V-GB1(No.2 sub)
06
07
TB5
TB5
TB5
106
Group 3
Group 4
46
TM4
PZ-60
DR-E
08
107
264