4. Outdoor Installation
4-3-4. Installation
When the pipes and/or cables are routed at the bottom of the unit, make sure that the through hole at the base of
the unit does not get blocked with the installation base.
When the pipes are routed at the bottom of the unit, the base should
· RP200-RP350
221 150
[8-23/32] [5-29/32]
251
83
[9-29/32] [3-9/32]
186
[7-11/32]
Refrigerant service
valve <liquid>
Refrigerant service
valve <gas>
80
760 [29-15/16]
(Mounting pitch)
[3-5/32]
Bottom view
Installation base perpendicular to the unit's front panel
4-3-5. Refrigerant pipe routing
Filler plate
(not supplied)
(Unit : mm [in.])
2X2-14X20 Oval hole
PUHY-RP200YJM-B(-BS)
PUHY-RP250YJM-B(-BS)
PUHY-RP300YJM-B(-BS)
80
[3-5/32]
PUHY-RP350YJM-B(-BS)
The gaps around the edges of through holes for pipes and wires on the
unit allow water or mice to enter the unit and damage its parts. Close
these gaps with filler plates.
This unit allows two types of pipe routing:
• Bottom piping
• Front piping
To prevent small animals, water, and snow from
entering the unit and damage its parts, close the
gap around the edges of through holes for pipes
and wires with filler plates.
Fill the gap at the site
SYSTEM DESIGN
be at least 100 mm [3-15/16 in.] in height.
Model
145 [5-23/32]
150 [5-29/32]
CAUTION
234