Mitsubishi Electric PUHY-RP-Y(S)JM-B Data Book page 216

Table of Contents

Advertisement

2. M-NET control
2-4-3. System examples
2-4-3-3. MA remote controller, Multi-refrigerant-system, System Controller at TB7/TB3 side, Booster for long M-NET wiring
PUHY
OC
OS1
TB7
TB7
51
52
CN40
CN41
CN40
CN41
DipSW2-1
DipSW2-1
ON
ON
TB3
TB3
TB2
202
SC
Power supply unit
(PAC-SC51KUA)
*2
000 or 201
SC*3
203
*3
SC
*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
*2 System controller should connect to TB7 at Outdoor and use power supply unit together in Multi-Refrigerant-System.
For AG-150A, 24V DC should be used with the PAC-SC51KUA.
*3 When multiple system controllers are connected in the system, set the controller with more functions than others as a "main"
controller and others as "sub".
Make the setting to only one of the system controllers for "prohibition of operation from local remote controller".
NOTE:
1. Outdoor units OC, OS1 and OS2 in one refrigerant circuit system are automatically detected.
OC, OS1 and OS2 are ranked in descending order of capacity. If units are the same capacity, they are ranked in ascending order
of their address.
2. Address should be set to Indoor units, LOSSNAY and system controller.
3. M-NET power is supplied by the Outdoor unit at TB3, while Indoor unit and ME remote controller consume the M-NET power for
transmission use. The power balance is needed to consider for long M-NET wiring. Details refer to 2-3 "System configuration restrictions".
PUHY
OS2
OC
TB7
TB7
53
91
CN40
CN41
CN40
CN41
DipSW2-1
DipSW2-1
ON
ON
TB3
TB3
Group 1
Indoor unit
01
02
TB5
TB15
TB5
*1
SRU
*3
MA R/C
*1
Wireless R/C
Group 31
Group 32
Indoor unit
41
42
TB5
TB15
TB5
*1
142
SRU
ME R/C
*1
Wireless R/C
SYSTEM DESIGN
PUHY
OS1
OC
TB7
TB7
92
98
CN40
CN41
CN40
CN41
DipSW2-1
DipSW2-1
ON
ON
TB3
TB3
Group 2
03
TB15
TB5
TB15
TB2
Transmission Booster
PAC-SF46EPA
Group 33
Group 34
LOSSNAY
43
45
TB5
TB5
143
MA R/C
PZ-52SF-E
Group 21
30
TB3
TB5
TB15
MA R/C
MA R/C
(Main)
(Sub)
Group 35
46
TB15
TB5
TB15
MA R/C
MA R/C
(Main)
(Sub)
Group 36
LOSSNAY
47
TB5
TM4
PZ-60
DR-E
213

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pury-rp-yjm-b

Table of Contents