4. Cooling [Ceiling cassette (2-way flow type)]
PLFY-P-VLMD-E
Model
Outdoor
size
air temp.
21.5°C D.B.
(Rated kW)
15°C W.B.
°C D.B.
CA
20.0
10.8
22.5
10.6
25.0
10.5
27.5
10.3
30.0
10.1
100
(11.2)
32.5
9.9
35.0
9.7
37.5
9.5
40.0
9.4
43.0
9.2
20.0
13.5
22.5
13.3
25.0
13.1
27.5
12.8
125
30.0
12.6
(14.0)
32.5
12.4
35.0
12.2
37.5
11.9
40.0
11.7
43.0
11.4
23°C D.B.
25°C D.B.
16°C W.B.
18°C W.B.
SHC
CA
SHC
CA
7.8
11.2
8.0
12.0
7.7
11.0
7.9
11.8
7.6
10.8
7.8
11.6
7.5
10.6
7.7
11.4
7.4
10.4
7.6
11.2
7.3
10.2
7.5
11.0
7.2
10.0
7.4
10.8
7.1
9.8
7.3
10.6
7.0
9.6
7.2
10.4
6.9
9.4
7.1
10.1
9.9
14.0
10.2
15.0
9.8
13.8
10.1
14.8
9.6
13.5
9.9
14.5
9.5
13.3
9.8
14.3
9.4
13.0
9.7
14.0
9.3
12.8
9.6
13.7
9.2
12.5
9.5
13.5
9.1
12.3
9.3
13.2
9.0
12.1
9.2
12.9
8.8
11.8
9.1
12.6
INDOOR UNITS
Indoor air temp.
27°C D.B.
28°C D.B.
19°C W.B.
20°C W.B.
SHC
CA
SHC
CA
8.0
12.5
8.4
12.9
7.9
12.2
8.3
12.6
7.8
12.0
8.2
12.4
7.7
11.8
8.1
12.2
7.6
11.6
8.0
12.0
7.5
11.4
8.0
11.8
7.4
11.2
7.9
11.5
7.3
10.9
7.8
11.3
7.2
10.7
7.7
11.1
7.1
10.5
7.6
10.8
10.2
15.6
10.7
16.1
10.0
15.3
10.6
15.8
9.9
15.0
10.5
15.5
9.8
14.8
10.4
15.3
9.7
14.5
10.3
15.0
9.6
14.2
10.1
14.7
9.4
14.0
10.1
14.4
9.3
13.7
9.9
14.1
9.2
13.4
9.8
13.9
9.1
13.1
9.7
13.5
CA:Capacity(kW) , SHC:Sensible Heat Capacity(kW)
30°C D.B.
32°C D.B.
22°C W.B.
24°C W.B.
SHC
CA
SHC
CA
8.4
13.7
8.3
14.6
8.3
13.5
8.2
14.4
8.2
13.3
8.1
14.1
8.1
13.0
8.0
13.8
8.0
12.8
7.9
13.6
7.9
12.5
7.8
13.3
7.8
12.3
7.8
13.1
7.7
12.1
7.7
12.8
7.6
11.8
7.6
12.6
7.5
11.5
7.5
12.3
10.7
17.2
10.6
18.3
10.6
16.9
10.5
17.9
10.5
16.6
10.4
17.6
10.3
16.3
10.2
17.3
10.2
16.0
10.1
17.0
10.1
15.7
10.0
16.7
10.0
15.4
9.9
16.4
9.9
15.1
9.8
16.0
9.8
14.8
9.7
15.7
9.6
14.4
9.5
15.4
kcal/h=kW x 860 , BTU/h = kW x 3,412
SHC
8.2
8.1
8.0
7.9
7.8
7.7
7.6
7.6
7.5
7.4
10.5
10.3
10.2
10.1
10.0
9.9
9.8
9.7
9.5
9.4
131