2. M-NET control
2-4-3. System examples
Factory setting
Original switch setting of the outdoors, indoors, controllers, LMAP and BM ADAPTER at shipment is as follows.
• Outdoor unit
• Indoor unit
• BC controller
• ME remote controller : Address: 101
• LMAP
• BM ADAPTER
Setting at the site
• DipSW2-1(Outdoor)
• DipSW4-6(BC controller) : Set DipSW 4-6 to ON at BC controller, in case of connected Indoor unit sized P100-P140 with 2 ports.
• DipSW1-2(LMAP)
• CN40/CN41
2-4-3-1. MA remote controller, Single-refrigerant-system, No System Controller
PURY
OC
00
CN40
CN41
DipSW2-1
OFF
TB3
BC controller
00
TB02
*1 For Wireless R/C and Signal receiver unit (SRU), channel 1, 2 and 3 are selectable and should be set to same channel.
NOTE:
1. No address setting is needed.
2. For a system having more than 32 indoor unit (P15-P140), confirm the need of Booster at 2-3 "System configuration
restrictions".
3. Indoor units should be set with a branch number.
4. Address setting is required if a sub BC controller is connected.
: Address: 00, CN41: U (Jumper), DipSW2-1: OFF
: Address: 00
: Address: 00
: Address: 247, CN41: U (Jumper), DipSW1-2: OFF
: Address: 00
: When the System Controller is used, all the Dip SW2-1 at the outdoor units should be set to
"ON". * Dip SW2-1 remains OFF when only LMAP02-E is used.
It is also possible to connect Indoor unit sized P100-P140 with 1 port (set DipSW 4-6 to OFF).
: When the LMAP is used together with System Controller, DipSW1-2 at the LMAP
should be set to "ON".
: Change jumper from CN41 to CN 40 at outdoor control board will activate central transmission
power supply to TB7;
(Change jumper at only one outdoor unit when activating the transmission power supply
without using a power supply unit.)
Change jumper from CN41 to CN 40 at LMAP will activate transmission power supply to LMAP
itself;
Power supply unit is recommended to use for a system having more than 1 outdoor unit,
because the central transmission power supply from TB7 of one of outdoor units is risking that
the outdoor unit failure may let down the whole system controller system.
Group 1
Indoor unit
00
00
TB5
TB15
TB5
1*
SRU
1*
Wireless R/C
SYSTEM DESIGN
Group 2
00
TB15
TB5
TB15
TB5
MA R/C
Group 3
Group 4
00
00
TB15
TB5
TB15
MA R/C
MA R/C
MA R/C
(Main)
(Sub)