Correction By Refrigerant Piping Length - Mitsubishi Electric PUHY-RP-Y(S)JM-B Data Book

Table of Contents

Advertisement

6. CAPACITY TABLES

6-3. Correction by refrigerant piping length

CITY MULTI system can extend the piping flexibly within its limitation for the actual situation. Yet, a decrease of cooling/heating
capacity could happen correspondently. Using following correction factor according to the equivalent length of the piping shown at
6-3-1 and 6-3-2, the capacity can be observed. 6-3-3 shows how to obtain the equivalent length of piping.
6-3-1. Cooling capacity correction
PUHY-RP200YJM-B(-BS)
1
0.95
0.90
0.85
0.80
0.75
0.70
0
20
40
60
Piping equivalent length (m)
PUHY-RP250YJM-B(-BS)
1
0.95
0.90
0.85
0.80
0.75
0.70
0
20
40
60
Piping equivalent length (m)
PUHY-RP300YJM-B(-BS)
1
0.95
0.90
0.85
0.80
0.75
0.70
0
20
40
60
Piping equivalent length (m)
PUHY-RP350YJM-B(-BS)
1
0.95
0.90
0.85
0.80
0.75
0.70
0
20
40
60
Piping equivalent length (m)
Total capacity of indoor unit
100
150
200
260
80
100
120
140
Total capacity of indoor unit
125
188
250
325
80
100
120
140
Total capacity of indoor unit
150
225
300
390
80
100
120
140
Total capacity of indoor unit
175
263
350
455
80
100
120
140
OUTDOOR UNITS
PUHY-RP400YSJM-B(-BS)
1
0.95
0.90
0.85
0.80
0.75
0.70
0
20
40
60
Piping equivalent length (m)
PUHY-RP450YSJM-B(-BS)
1
0.95
0.90
0.85
0.80
0.75
0
20
40
60
Piping equivalent length (m)
PUHY-RP500YSJM-B(-BS)
1
0.95
0.90
0.85
0.80
0.75
0.70
0
20
40
60
Piping equivalent length (m)
PUHY-RP550YSJM-B(-BS)
1
0.95
0.90
0.85
0.80
0.75
0.70
0
20
40
60
Piping equivalent length (m)
Total capacity of indoor unit
200
300
400
520
80
100
120
140
Total capacity of indoor unit
225
338
450
585
80
100
120
140
Total capacity of indoor unit
250
375
500
650
80
100
120
140
Total capacity of indoor unit
275
413
550
715
80
100
120
140
43