6. CAPACITY TABLES
PUHY-
RP450YSJM-B RP500YSJM-B
Nominal
kW
50.0
Cooling
BTU/h
170,600
Capacity
Input
kW
13.77
PUHY-
RP550YSJM-B P600YSJM-B
Nominal
kW
63.0
Cooling
BTU/h
215,000
Capacity
Input
kW
17.50
PUHY-
RP650YSJM-B
Nominal
kW
73.0
Cooling
BTU/h
249,100
Capacity
Input
kW
21.09
(There is no difference in cooling performance
between Standard Mode and COP Priority Mode.)
PUHY-
RP450YSJM-B RP500YSJM-B
Nominal
kW
56.0
Heating
BTU/h
191,100
Capacity
Input
kW
12.81
PUHY-
RP550YSJM-B RP600YSJM-B
Nominal
kW
69.0
Heating
BTU/h
235,400
Capacity
Input
kW
16.62
PUHY-
RP650YSJM-B
Nominal
kW
81.5
Heating
BTU/h
278,100
Capacity
Input
kW
21.73
1.4
56.0
1.3
191,100
15.68
1.2
1.1
69.0
1.0
235,400
18.59
0.9
0.8
0.7
0.6
1.2
1.1
1.0
0.9
0.8
0.7
0.6
0.5
0.4
-5
0
23
32
1.4
63.0
1.3
215,000
1.2
14.44
1.1
76.5
1.0
261,000
0.9
19.22
0.8
0.7
0.6
0.5
0.4
1.2
1.1
1.0
0.9
0.8
0.7
0.6
0.5
0.4
-20
-15
-4
OUTDOOR UNITS
5
10
15
20
41
50
59
68
Ratio of cooling capacity and power input
-10
-5
5
14
23
Ratio of heating capacity and power input
Indoor Temperature
25
30
35
40
77
86
95
104
Outdoor Temperature
Indoor Temperature
0
5
10
32
41
50
Outdoor Temperature
24°CWB
75°FWB
22°CWB
72°FWB
20°CWB
68°FWB
18°CWB
64°FWB
16°CWB
61°FWB
15°CWB
59°FWB
24°CWB
75°FWB
22°CWB
72°FWB
20°CWB
68°FWB
18°CWB
64°FWB
16°CWB
61°FWB
15°CWB
59°FWB
45
°CDB
113
°FDB
15°CDB
59°FDB
20°CDB
68°FDB
25°CDB
77°FDB
27°CDB
80°FDB
15°CDB
59°FDB
20°CDB
68°FDB
25°CDB
77°FDB
27°CDB
80°FDB
15
°CWB
59
°FWB
32