7.8 Restrictions for special ambient conditions

7.8
Restrictions for special ambient conditions
Maximum current at low speeds
NOTICE
Overheating the inverter due to unsuitable load
Loading the inverter with a high output current and at the same time with a low output
frequency can cause the current-conducting components in the inverter to overheat.
Excessively high temperatures can damage the inverter or have a negative impact on the
inverter service life.
● Never operate the inverter continuously with an output frequency = 0 Hz.
● Only operate the inverter in the permissible operating range.
Figure 7-2
● Continuous operation:
Operating state that is permissible for the complete operating time.
● Short-time duty:
Operating state that is permissible for less than 2 % of the operating time.
● Sporadic short-time duty:
Operating state that is permissible for less than 1 % of the operating time.
108
Permissible operating range of the inverter
Hardware Installation Manual, 08/2017, A5E33294624B AG
Power Module PM240-2