7.2

Ambient conditions

Property
Ambient conditions for transport in the transport packaging
Climatic ambient conditions
Mechanical ambient condi‐
tions
Protection against chemical
substances
Biological ambient condi‐
tions
Ambient conditions for long-term storage in the product packaging
Climatic ambient conditions
Protection against chemical
substances
Biological ambient condi‐
tions
Ambient conditions in operation
Installation altitude
Climatic ambient conditions
1)
Mechanical ambient condi‐
tions
Protection against chemical
substances
Power Module PM240-2
Hardware Installation Manual, 08/2017, A5E33294624B AG
Version
‑ 40° C ... + 70° C, according to Class 2K4 to EN 60721‑3‑2
maximum humidity 95% at 40° C
● FSA ... FSC: Shock and vibration permissible according to 1M2 to EN 60721‑3‑2
● FSD ... FSF: Shock and vibration permissible according to 2M3 to EN 60721‑3‑2
Protected according to Class 2C2 to EN 60721‑3‑2
Suitable according to Class 2B1 to EN 60721‑3‑2
‑ 25° C ... + 55° C, according to Class 1K3 to EN 60721‑3‑1
Protected according to Class 1C2 to EN 60721‑3‑1
Suitable according to class 1B1 to EN 60721‑3‑1
Up to 1000 m above sea level without limitations
Restrictions for special ambient conditions (Page 108)
● FSA ... FSC ambient operating temperature
For operation according to Low Overload: -10° C ... +40° C
For operation according to High Overload: -10° C ... +50° C
Restrictions for special ambient conditions (Page 108)
● FSD ... FSF ambient operating temperature
For operation according to Low Overload: -20° C ... +40° C
For operation according to High Overload: -20° C ... +50° C
Restrictions for special ambient conditions (Page 108)
● Relative humidity: 5 ... 95%, condensation not permitted
● Oil mist, salt mist, ice formation, condensation, dripping water, spraying water, splashing
water and water jets are not permitted
Shock and vibration permissible, according to Class 3M1 to EN 60721‑3‑3
Vibration test during operation according to IEC 60068-2-6 Test Fc (sinusoidal)
● 0 ... 57 Hz: 0.075 mm deflection amplitude
● 57 ... 150 Hz: 1 g acceleration amplitude
● 10 frequency cycles per axis
Shock test according to IEC 60068-2-27 Test Ea (half-sine)
● 5 g peak acceleration
● 30 ms duration
● 3 shocks in all three axes in both directions
● FSA ... FSC: Protected according to 3C2 to EN 60721‑3‑3
● FSD ... FSF: 3C3 protection according to EN 60721‑3‑3
7.2 Ambient conditions