Technical data of the braking resistor

For the inverters, use the following or comparable braking resistors. The technical properties
and statements made by the manufacturer apply.
Note
Braking resistors FSD ... FSF
Only use braking resistors that are UL approved, and have successfully passed the "Abnormal
Operation Test" according to UL 508.
Braking resistors for PM240-2, 200 V
Table 9-6
Technical data
Article number
JJY:023146720008
JJY:023151720007
JJY:02 3163720018
JJY:023433720001
JJY:023422620002
JJY:023423320001
JJY:023434020003
Power Module PM240-2
Hardware Installation Manual, 08/2017, A5E33294624B AG
Resist‐
Maximum
ance
power, P
max
Rated power
P
db
200 Ω
0.75 kW
37.5 W
68 Ω
2.2 kW
110 W
37 Ω
4 kW
200 W
20 Ω
7.5 kW
375 W
7.5 Ω
18.5 kW
930 W
4.5 Ω
30 kW
1500 W
2.5 Ω
55 kW
2750 W
Connection
Degree of
R1 / R2
protection
Weight
Connecting cable
IP20
integrated in the
1.5 kg
braking resistor
IP20
1.8 kg
IP20
2.7 kg
IP20
6.2
10 mm
/ 0.5 Nm
IP21
2
8 AWG / 4.5 lbf in
7.0 kg
16 mm
/ 1.2 Nm
IP21
2
6 AWG / 10.6 lbf in
8.5 kg
16 mm
/ 1.2 Nm
IP21
2
6 AWG / 10.6 lbf in
13.5 kg
Accessories
9.6 Braking resistor
Power Module
Article numbers
6SL3210-1PB13-0 . L0
6SL321 . -1PB13-8 . L0
6SL3210-1PB15-5 . L0
6SL3210-1PB17-4 . L0
6SL321 . -1PB21-0 . L0
6SL3210-1PB21-4 . L0
6SL321 . -1PB21-8 . L0
6SL3210-1PC22-2 . L0
6SL3210-1PC22-8 . L0
6SL3210-1PC24-2 . L0
6SL3210-1PC25-4 . L0
6SL321 . -1PC26-8 . L0
6SL3210-1PC28-0 . L0
6SL321 . -1PC31-1 . L0
6SL3210-1PC31-3 . L0
6SL3210-1PC31-6 . L0
6SL321 . -1PC31-8 . L0
Frame
size
FSA
FSB
FSC
FSC
FSD
FSE
FSF
135