Additional requirements relating to CSA conformance, frame sizes FSD ... FSF
Overvoltage category OVC III must be ensured for all connections of the power circuit. This
can mean that a surge suppressor must connected upstream on the line side. The rated
voltage of the surge suppressor must not exceed the line voltage, and must guarantee the
limit values (VPR) specified here.
Line voltage
3 AC 200 V ... 240 V
3 AC 380 V ... 480 V
3 AC 500 V ... 600 V
Power Module PM240-2
Hardware Installation Manual, 08/2017, A5E33294624B AG
Grounded neutral conductor 139 V
Grounded line conductor
Grounded neutral conductor 277 V
Grounded line conductor
Grounded neutral conductor 347 V
Grounded line conductor
4.1 Installation conditions
Phase to ground
Phase to phase
Rated
VPR
Rated
voltage
voltage
2.5 kV
240 V
240 V
4 kV
240 V
4 kV
480 V
480 V
6 kV
480 V
6 kV
600 V
600 V
6 kV
600 V
Installing/mounting
VPR
4 kV
4 kV
4 kV
4 kV
4 kV
4 kV