7.2.2. RECORDING: setting of Typical Configurations

The following "Typical Configurations" are selectable via RECORDER CONFIG menu:
Standard Configuration
LEAKAGE (I1)
To activate the above configuration, follow this procedure:
1. Turn the rotary switch to "AUX".
2. Press MENU key. Use the F1 key to display the screen below:
3. Press MENU key again. The instrument displays a screen as shown below (picture on
the left). In this way it is possible to select the desired configuration on I1 channel with
F1 or F2 key. NOTE that TEMP and HUMIDITY are not supported.
TYPICAL
LEAKAGE(I1)
TEMP.°C(I1)
HUM %HR(I1)
Configuration selection
4. Press ENTER key. The instrument displays the message "Data saved" for a while to
confirm the desired configuration (see above picture on the right). The instrument will
return to the measuring mode and you can start recording by pressing START/STOP
key.
Setting of measuring and recording mode of Leakage current on I1 channel.
MENU GENERAL
SAFETY TEST MEMORY
ANALYZER MEMORY
RESET
ANALYZER CONFIG
RECORDER CONFIG
CONTRAST
DATE&TIME
LANGUAGE
CONFIG.
Page 61 of 131
Description
TYPICAL
CONFIG.
LEAKAGE (I1)
TEMP.°C(I1)
HUM %HR(I1)
Data saved
Confirmation configuration selection
VR2250