Practical Reports For Electrical Tests; Continuity Test On Protective Conductors - MARTINDALE VR2250 User Instruction Manual

Multifunction test instrument
Table of Contents

Advertisement

16.

PRACTICAL REPORTS FOR ELECTRICAL TESTS

16.1.

Continuity Test On Protective Conductors

PURPOSE OF THE TEST
Check the continuity of:
NOTE: This test is to be preceded by a visual check verifying the existence of yellow-
green protective and equalising potential conductors as well as compliance of
the sections used with the standards' requirements.
INSTALLATION PARTS TO BE CHECKED
MARVR2250
Examples for continuity measurement on conductors
protective conductors (PE), main equalising potential
conductors (EQP), secondary equalising potential
conductors (EQS) in TT and TN-S systems.
Neutral conductors having functions of protective
conductors (PEN) in TN-C system.
MARVR2250
Page 107 of 131
VR2250
Connect one of the
test leads to the
protective
conductor of the
FM socket and the
other to the
equalising potential
node of the earth
installation.
Connect one of the
test leads to the
external mass (in
this case the water
pipe) and the other
to the earth
installation using
for example the
protective
conductor of the
closest FM socket.

Advertisement

Table of Contents
loading

Table of Contents