6.3.2. Measurement procedure
1. Select the desired test parameter by means of the F1, F2, F3, F4 key.
2. Connect the Red, Green and Black connectors of the three-terminal mains cable or
of the split cables to the corresponding input terminals of the instrument B1, B3, B4
Red
Instrument connection for 230V single-phase
RCD check
1
3
N
Green
Black
Instrument connection for 400V + N (no PE)
three-phase RCD check
3. Connect the mains plug or the Test leads to the System under test according to
one of the diagrams above.
P
I1
B1
B2
B3
B4
Green
Black
Red
I1
B4
B1
B2
B3
Page 28 of 131
1
3
N
Black
B1
Instrument connection for 400V + N + PE
three-phase RCD check
1
3
Black
B1
Instrument connection for 400V + PE (no N)
three-phase RCD check