Integrating A Control Unit Into The Lon - Viessmann VITOLIGNO 300-P Service Instructions Manual

Pellet boiler
Table of Contents

Advertisement

Commissioning, inspection, maintenance
Further details regarding the individual steps
Changing slope and level
Individually adjustable for each heating
circuit.
110
+20
Outside temperature in °C
A Changing the slope
B Changing the level (vertical parallel
offset of the heating curve)
Press the following keys:
1. "MENU".

Integrating a control unit into the LON

The LON communication module
(accessory) must be plugged in.
Note
The data transfer via LON can take sev-
eral minutes.
Single boiler system with
Vitotronic 200-H
Set the LON subscriber numbers and
further functions via code 2.
44
3.5
1.4
A
B
0.2
-20
2. |/~ to select the heating circuit.
3. d
to confirm.
4. |/~ for "Heating curve".
5. d
to confirm.
6. |/~ for "Slope" or "Level".
7. d
to confirm.
8. |/~ for the required value.
9. d
to confirm.
10. With g back to the standard dis-
play.
See the following table.
Note
The same subscriber number cannot be
allocated twice within one LON system.
Only one Vitotronic may be program-
med as fault manager.
(cont.)