Viessmann VITOLIGNO 300-P Service Instructions Manual page 78

Pellet boiler
Table of Contents

Advertisement

Codes
Code 2
(cont.)
Coding in the delivered condition
Heating program
switches to "Constant
central heating with
reduced room tempera-
ture"
E1:1
With remote control:
Set day temperature
adjustable at the remote
control from 10 to 30 °C
E2:50
With remote control
No display correction of
the actual room tempera-
ture
F1:0
Screed function disabled F1:1
F2:8
Time limit for party mode
8 h or external operating
mode changeover via
key
Temperature limit for ter-
F8:−5
minating reduced mode
−5 ºC; see example on
page 121.
Observe the setting of
coding address "A3".
Temperature limit for rais-
F9:−14
ing the reduced set room
temperature −14 ºC; see
example on page 121.
Party mode ends automatically in the "Heating and DHW" program, when the
*1
system changes over to operation with standard room temperature.
78
*1
Possible change
E1:0
Set day temperature
adjustable from 3 to 23 °C
E1:2
Set day temperature
adjustable from 17 to
37 °C
E2:0
Display correction –5 K
to
to
E2:49
Display correction –0.1 K
E2:51
Display correction +0.1 K
to
to
E2:99
Display correction +4.9 K
Screed function adjustable
to
in accordance with 6
F1:6
selectable temperature/
time profiles (see
page 126)
F2:0
No time limit for party
mode
F2:1
Time limit adjustable from 1
to
to 12 h
F2:12
F8:+10
Temperature limit adjusta-
ble from +10 to −60 °C
to
F8:−60
Function disabled
F8:−61
F9:+10
Temperature limit adjusta-
ble from +10 to −60 °C
to
F9:−60
*1
*1