Code 2
(cont.)
Coding in the delivered condition
55:0
Without DHW cylinder
56:0
Set DHW temperature
adjustable from 10 to
60 °C
58:0
Without auxiliary function
for DHW heating
59:0
Cylinder heating
Start point: Set value
−2.5 K
Stop point: Set value
+2.5 K
5A:0
No function
60:15
During DHW heating, the
boiler water temperature
is max. 15 K higher than
the set DHW tempera-
ture
61:0
Cylinder heating subject
to the buffer cylinder or
boiler water temperature
62:10
Circulation pump with
max. 10 min run-on
Possible change
Automatic recognition
55:1
Cylinder heating,
hysteresis ± 2.5 K
55:2
Adaptive cylinder heating
active
56:1
Set DHW temperature
adjustable from 10 to
75 °C
58:1
Entry of a 2nd set DHW
to
temperature, adjustable
58:75
from 10 to 75 °C (observe
coding address "56")
59:1
Start point adjustable from
to
1 to 10 K below the set
59:10
value
5A:1
Flow temperature demand
from the DHW cylinder is
the maximum system
value
60:10
The differential between
to
the boiler water tempera-
60:50
ture and the set DHW tem-
perature is adjustable from
10 to 50 K
61:1
Cylinder heating independ-
ent of temperature
61:2
Code "45:2" must be selec-
ted:
Cylinder heating subject to
the boiler water tempera-
ture
62:0
Circulation pump without
run-on
62:1
Max. run-on time adjusta-
to
ble from 1 to 15 min
62:15
Codes
67