Integrating A Control Unit Into The Lon - Viessmann Vitoligno 300-P Service Instructions For Contractors

Pellet boiler
Table of Contents

Advertisement

Commissioning, inspection, maintenance
Further details regarding the individual steps
Changing slope and level
Individually adjustable for each heating
circuit.
110
+20
Outside temperature in °C
A Changing the slope
B Changing the level (vertical parallel
offset of the heating curve)
Press the following keys:
1. "MENU".

Integrating a control unit into the LON

The LON communication module
(accessory) must be plugged in.
Note
The data transfer via the LON system
can take several minutes.
Single boiler system with
Vitotronic 200-H
Set up the LON user numbers and fur-
ther functions via code 2.
34
3.5
1.4
A
B
0.2
-20
(cont.)
2. |/~ for selecting the heating cir-
cuit.
3. d
to confirm.
4. |/~ for "Heating curve".
5. d
to confirm.
6. |/~ for "Slope" or "Level".
7. d
to confirm.
8. |/~ for the selected value.
9. d
to confirm.
10. With g back to the standard dis-
play.
See the following table.
Note
In the same LON system, the same user
number cannot be allocated twice.
Only one Vitotronic may be program-
med as fault manager.