Viessmann VITOLIGNO 300-P Service Instructions Manual page 90

Pellet boiler
Table of Contents

Advertisement

Troubleshooting
Fault display
Displayed
System characteris-
fault code
tics
94
Solar circuit pump
switched off; no cylin-
der heating through
the solar thermal sys-
tem.
Collector frost protec-
tion function starts, if
enabled and if
required
9A
Solar circuit pump
switched off; no cylin-
der heating through
the solar thermal sys-
tem.
Collector frost protec-
tion function starts, if
enabled and if
required
9B
Solar circuit pump
switched off; no cylin-
der heating through
the solar thermal sys-
tem.
Collector frost protec-
tion function starts, if
enabled and if
required
9C
Solar circuit pump
switched off; no cylin-
der heating through
the solar thermal sys-
tem.
Collector frost protec-
tion function starts, if
enabled and if
required
90
(cont.)
Cause
Short circuit, cylin-
der temperature
sensor
External Vitosolic
solar control unit:
Connection to S2
Lead break, collec-
tor temperature
sensor
External Vitosolic
solar control unit:
Connection to S1
Lead break, tem-
perature sensor
External Vitosolic
solar control unit:
Connection to S3
Lead break, cylin-
der temperature
sensor
External Vitosolic
solar control unit:
Connection to S2
Measures
Check the cylinder tem-
perature sensor (see
page 96)
Check collector tempera-
ture sensor (see
page 96)
Check temperature sen-
sor (see page 96)
Check the cylinder tem-
perature sensor (see
page 96)