Code 2
(cont.)
Coding in the delivered condition
BB:1
Buffer heating priority
BC:1
Forced heat transfer
when exceeding the max.
boiler water temperature.
The mixer regulates to
the set flow temperature
and DHW heating is ena-
bled.
C3:125
Mixer runtime 125 s
C4:1
System dynamics
Mixer control characteris-
tics
C5:20
Electronic minimum flow
temperature limit set to
20 °C
(only during operation
with standard room tem-
perature)
C6:75
Electronic maximum flow
temperature limit set to
75 °C
C8:31
With remote control unit
and for the heating circuit,
operation with room tem-
perature hook-up must be
programmed:
Without room influence
D5:0
With external heating pro-
gram changeover:
Possible change
B5:1
For heating circuit pump
to
logic function, see the table
B5:8
on page 59:
BB:0
No buffer heating priority
BC:0
No forced heat transfer
C3:10
Runtime adjustable from
to
10 to 255 s
C3:255
C4:0
Controller responds too
to
quickly (cycles between
C4:3
"Open" and "Close"):
Select a lower value
Controller responds too
slowly (temperature is not
held sufficiently):
Select a higher value
C5:1
Minimum limit adjustable
to
from 1 to 127 °C
C5:127
C6:10
Maximum limit adjustable
to
from 10 to 127 °C
C6:127
C8:1
Room influence limit
to
adjustable from 1 to 30 K
C8:30
D5:1
Heating program switches
to "Constant central heat-
ing with standard room
temperature"
Codes
77