Code 2
(cont.)
Coding in the delivered condition
98:1
Viessmann system num-
ber (in conjunction with
monitoring several sys-
tems via Vitocom 300)
99:0
Connection at terminals 2
and 3 in plug aVD disa-
bled (external blocking/
external "Mixer close")
(see page 126)
9A:0
Connection at terminals 1
and 2 in plug aVD disa-
bled (external "Mixer
open") (see page 125)
9B:0
No default minimum flow
temperature
9C:20
Monitoring LON subscrib-
ers:
If there is no response
from a subscriber, values
specified by the control
unit are used after
20 min and a fault mes-
sage is issued
9D:0
Without function exten-
sion 0 - 10 V
Possible change
98:1
System number adjustable
to
from 1 to 5
98:5
99:1
External "Mixer close"
Heating circuit 1
99:2
External "Mixer close"
Heating circuit 2
99:3
External "Mixer close"
Heating circuits 2 and 3
99:4
External blocking
99:5
External blocking/external
"Mixer close"
Heating circuit 1
99:6
External blocking/external
"Mixer close"
Heating circuit 2
99:7
External blocking/external
"Mixer close"
Heating circuits 1 and 2
9A:1
External "Mixer open"
Heating circuit 1
9A:2
External "Mixer open"
Heating circuit 2
9A:3
External "Mixer open"
Heating circuits 1 and 2
9B:1
Set minimum flow temper-
to
ature in the case of external
9B:127
demand, adjustable from 1
to 127 °C (see page 125)
9C:0
No monitoring
9C:5
Time adjustable from 5 to
to
60 min
9C:60
9D:1
With function extension;
automatic recognition
Codes
73