Viessmann VITOLIGNO 300-P Service Instructions Manual page 70

Pellet boiler
Table of Contents

Advertisement

Codes
Code 2
(cont.)
Coding in the delivered condition
Max. collector start-up
temperature; the solar cir-
cuit pump is not started if
the collector temperature
exceeds 130 °C
6F:20
In conjunction with an
integral solar control unit
and coding address
"6E":
The solar circuit pump
only starts when the col-
lector temperature has
fallen 20 K below the col-
lector start-up tempera-
ture
70:0
DHW circulation pump
"ON" according to time
program when DHW
heating is enabled
71:0
DHW circulation pump:
"ON" according to time
program
72:0
DHW circulation pump:
"ON" according to time
program
73:0
DHW circulation pump:
"ON" according to time
program
75:0
DHW circulation pump
"ON" during economy
mode according to time
program
76:0
Without LON communi-
cation module
77:1
LON subscriber number
70
Possible change
6E:200
Without collector start-up
limit
6F:10
Value adjustable from 10 to
to
50 K
6F:50
70:1
DHW circulation pump
"ON" according to time pro-
gram
71:1
"OFF" during DHW heating
to the first set value
71:2
"ON" during DHW heating
to the first set value
72:1
"OFF" during DHW heating
to the second set value
72:2
"ON" during DHW heating
to the second set value
73:1
During time program
to
1x/h for 5 min "ON"
73:6
to
6x/h for 5 min "ON"
73:7
Constantly "ON"
75:1
DHW circulation pump
"OFF" during economy
mode according to time
program
76:1
With LON communication
module;
automatic recognition
77:1
LON subscriber number,
to
adjustable from 1 to 99