Viessmann VITOLIGNO 300-P Service Instructions Manual page 72

Pellet boiler
Table of Contents

Advertisement

Codes
Code 2
(cont.)
Coding in the delivered condition
The circulation pump for
cylinder heating stops
when the boiler water/
buffer cylinder tempera-
ture (top sensor) falls
below the actual cylinder
temperature by the differ-
ential comprising the val-
ues of coding addresses
"84" and "85"
86:130
In conjunction with an
integral solar control
unit:
The solar circuit pump
stops when the collector
temperature exceeds
130 °C
8A:175
Do not adjust
90:128
Time constant for calcu-
lating the adjusted out-
side temperature 21.3 h
91:0
Connection at terminals 1
and 2 in plug aVD disa-
bled (external heating
program changeover)
(see page 125)
94:0
Do not adjust
95:0
Without Vitocom 100
96:0
Do not adjust
97:0
With LON communication
module:
The outside temperature
of the sensor connected
to the control unit is only
utilised internally
72
Possible change
86:110
The solar circuit pump
to
stops when the collector
86:199
temperature exceeds the
selected value; adjustable
from 110 to 199 °C
86:200
Without collector limit tem-
perature shutdown
90:1
Fast (low values) or slow
to
(high values) matching of
90:199
the flow temperature, sub-
ject to the set value when
the outside temperature
changes;
1 step ≙ 10 min
91:1
Contact affects the follow-
ing heating circuits:
Heating circuit 1
91:2
Heating circuit 2
91:3
Heating circuits 1 and 2
95:1
With Vitocom 100;
automatic recognition
97:1
The control unit receives
the outside temperature
from the LON subscriber
97:1
The control unit transmits
the outside temperature to
the LON subscriber