8.3.2
In the object error code, the last error which has occurred is stored.
According to DS402, a large number of possible error reports have been specified. The
following list shows the interconnection between the error code displayed internally by
the frequency inverter and displayed on control unit KP500 and the error secured in
the object error code.
F00 xx
F01 xx
F02 xx
F03 xx
F04 xx
F05 xx
F07 xx
F08 xx
F13 xx
Fyy xx
If 1000 = generic error appears as the error code, the error code can be read off via
parameter
code in the product-internal format.
The assignment table of the error code to the reports in question can be seen from
the operating instructions.
In the emergency message, the error code of the frequency inverter is transmitted on
bytes 4 ... 7.
06/05
06/05
0x603F/0 error code (integer 16)
Error
Error code
00
00 No error has occurred
23
10 Frequency inverter has been overloaded
42
10 Case temperature outside the temperature limits
41
10 Inside temperature outside the temperature limits
43
10 Motor temperature too high or sensor defective
23
40 Motor phase current above the current limit
32
10 DC link voltage outside the voltage range
51
11 Electronic voltage outside the voltage range
23
30 Earth fault on frequency inverter output
10
00 Other error reports
Current error
Error reports
Overload
Case
Inside
Motor connection
Output current
DC link voltage
Electronic voltage
Motor connection
Generic error
Current error
260. The parameter
Meaning
260 contains the error
19
19