Activating Autonomous Drive Emergency Retraction In Case Of; Plc Failure Or 5 V Undervoltage (As From Sw 6.3) - Siemens SINUMERIK 840C Installation Instructions Manual

Hide thumbs Also See for SINUMERIK 840C:
Table of Contents

Advertisement

01.99
12.20.8.2
No NCK failure, activation only when in operative mode, no run up in the general reset mode
Activating
Clearing for activation of the autonomous drive emergency retraction is implemented according
to the function via the following MD bits:
NC MD
5022
5022.4=1
5022.5=1
5022.7=1
5022.7=0
Default setting of bit is 0.
Reactions
Display of the applicable alarm on (POWER ON), stopping the NCK CPU and execution of the
autonomous drive emergency retraction.
After POWER ON, the NCK instantly runs in normal operational mode instead of the then
startup mode.
© Siemens AG 1992 All Rights Reserved
SINUMERIK 840C (IA)
More user manuals on
Activating autonomous drive emergency retraction in
case of PLC failure or 5 V undervoltage (as from SW 6.3)
7
6
Delay of the
NC ready
signal for
1 IPO cycle
5 V under-
in case of
voltage
PLC failure
or 5 V
under-
voltage
Clearing for activation of the autonomous drive emergency retraction in case
of PLC failure
Clearing for activation of the autonomous drive emergency retraction in case
of 5 V undervoltage
Delay of the NC ready signal for 1 IPO cycle in case of PLC failure of 5 V
undervoltage
No delay of the NC ready signal for 1 IPO cycle in case of PLC failure or 5 V
undervoltage
ManualsBase.com
12.20.8 Configuration help for generator operation and emergency retraction
Bit No.
5
4
3
Retraction in
case of PLC
failure
6FC5197- AA50
12 Functional Descriptions
2
1
0
12–231