NETWORK SETTINGS

HTTP protocol

98
To use SNTP in broadcast mode, program this setting to "0.0.0.0". The D90
to SNTP messages sent to the all ones broadcast address for the subnet. The
Plus
D90
waits up to eighteen minutes (1024 seconds) without receiving an SNTP
broadcast message before signaling an SNTP self-test error.
UDP Port Number
Range: 0 to 65535 in steps of 1
Default: 123
This setting specifies the UDP port number for use with the SNTP protocol.
Ethernet Interface
Range: 1, 2, or 3
Default: 1
This setting selects the Ethernet port to use for SNTP communications.
Plus
The D90
contains an embedded web server and is capable of transferring web pages to
a web browser. The web pages are organized as a series of menus that can be accessed
Plus
starting at the D90
main menu. Web pages are read-only and are available showing
DNP and IEC 60870-5-104 points lists, Modbus registers, event records, fault reports, and
so on. The main menu will be displayed in the web browser on the computer simply by
entering the IP address of the D90
Select the Settings > Communications > Network > HTTP menu item to open the HTTP
configuration window.
Plus
into the address field on the web browser.
Figure 77: Example web access page
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 6: COMMUNICATIONS
Plus
then listens