GE D90 Plus Instruction Manual page 245

Line distance protection system
Hide thumbs Also See for D90 Plus:
Table of Contents

Advertisement

CHAPTER 7: PROTECTION
Neutral time overcurrent
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Block When Voltage Memory Expires
Range: Yes, No
Default: No
This setting is used to select the required operation upon expiration of voltage memory.
When set to "Yes", the directional element blocks the operation of any phase overcurrent
element under directional control, when voltage memory expires; when set to "No", the
directional element allows tripping of phase overcurrent elements under directional
control.
Events
Range: Enabled, Disabled
Plus
Default: varies with UR
This setting enables and disables the logging of phase directional overcurrent events in
the sequence of events recorder.
The logic for the phase directional overcurrent 1 element is shown below. The logic is
identical for all phase directional overcurrent elements.
Figure 205: Phase directional overcurrent 1 scheme logic
The neutral time overcurrent element can provide a desired time-delay operating
characteristic versus the applied current or be used as a simple definite time element. The
neutral current input value is a quantity calculated as 3I_0 from the phase currents and
may be programmed as fundamental phasor magnitude or total waveform RMS
magnitude as required by the application.
Two methods of resetting operation are available: timed and instantaneous. When the
element is blocked, the time accumulator will reset according to the reset characteristic.
For example, if the element reset characteristic is instantaneous and the element is
blocked, the time accumulator will be cleared immediately.
-series model; refer to the EnerVista UR
GROUPED PROTECTION ELEMENTS
Plus
Setup software
235

Advertisement

Table of Contents
loading

Table of Contents