Dielectric Strength; Main Processor Module - GE D90 Plus Instruction Manual

Line distance protection system
Hide thumbs Also See for D90 Plus:
Table of Contents

Advertisement

ELECTRICAL INSTALLATION

Dielectric strength

Main processor module

Ethernet port
DANGER:
CAUTION:
52
The dielectric strength of the UR
table.
Table 1: Dielectric strength for UR
Function
Terminals
from
Power supply module
high (+), low (+), (–)
Power supply module
48 V DC (+) and (–)
Power supply module
relay terminals
Main CPU
RS485 port
Main CPU
RJ45 port
Main CPU
IRIG-B port
Front panel
USB port
Contact inputs/outputs
all
AC module
all
Communications module
RS45 ports
G.703 module
all except 1a, 8a
RS422 module
all except 1a, 8a
Filter networks and transient protection clamps are used in the hardware to prevent
damage caused by high peak voltage transients, radio frequency interference (RFI), and
electromagnetic interference (EMI). These protective components can be damaged by
application of the ANSI/IEEE C37.90 specified test voltage for a period longer than the
specified one minute.
The main processor module contains ports for Ethernet communications, serial RS485
communications, and IRIG-B connection.
The fiber optic communication ports allow for fast and efficient communications between
relays at 100 Mbps. Optical fiber may be connected to the relay supporting a wavelength
of 1310 nm in multi-mode.
The optical fiber sizes supported are 50/125 µm and 62.5/125 µm. The fiber optic port is
designed such that the response times will not vary for any core that is 62.5 µm or less in
diameter. For optical power budgeting, splices are required every 1 km for the transmitter-
receiver pair. When splicing optical fibers, the diameter and numerical aperture of each
fiber must be the same. In order to engage or disengage the ST type connector, only a
quarter turn of the coupling is required.
Observing any fiber transmitter output may cause injury to the eye!
Ensure the dust covers are installed when the fiber is not in use. Dirty or scratched
connectors can lead to high losses on a fiber link.
Plus
-series module hardware is shown in the following
Plus
-series hardware
to
chassis
chassis
chassis
chassis
chassis
chassis
chassis
chassis
chassis
chassis
chassis
chassis
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 3: INSTALLATION
Dielectric strength
2000 V AC for 1 minute
2000 V AC for 1 minute
2000 V AC for 1 minute
2000 V AC for 1 minute
1500 V AC for 1 minute
2000 V AC for 1 minute
2000 V AC for 1 minute
2000 V AC for 1 minute
2000 V AC for 1 minute
1500 V AC for 1 minute
1000 V AC for 1 minute
1500 V AC for 1 minute