CHAPTER 1: GETTING STARTED

EnerVista software

PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
To communicate through the D90
GE RS232/RS485 converter box is required. This device (catalog number F485) connects to
the computer using a straight-through serial cable. A shielded twisted-pair (20, 22, or 24
AWG) connects the F485 converter to the D90
terminals (+, –, GND) are connected to the D90
terminals. The line should be terminated with a 120 Ω, 1 nF R-C network.
Communications via Ethernet requires a connection to an Ethernet network using a
standard copper or fiber cable. The Ethernet port can also connect directly to a PC using a
cross-over cable.
To communicate via the faceplate USB port, a standard USB serial cable is used.
For additional information, refer to:
Main processor module
The EnerVista software suite is an industry-leading set of programs that simplifies every
Plus
aspect of the D90
. The EnerVista suite provides tools to monitor the status of your
protected asset, maintain the device, and integrate information measured by the
Plus
D90
into DCS or SCADA monitoring systems. Convenient COMTRADE and sequence of
events viewers are an integral part of the EnerVista UR
Plus
every D90
. This allows the user to carry out post-mortem event analysis to ensure
proper protection system operation.
Figure 4: Communications overview
Plus
rear RS485 port from a computer's RS232 port, the
Plus
rear communications port. The converter
Plus
communication module (+, –, COM)
on page 52.
ENERVISTA SOFTWARE
Plus
Setup software included with
7