GE D90 Plus Instruction Manual page 178

Line distance protection system
Hide thumbs Also See for D90 Plus:
Table of Contents

Advertisement

SHARED OPERANDS
168
RemDPS Ip 1 INTERM ...............................Asserted when remote double-point status input 1 is in the
RemDPS Ip 1 OFF.......................................Asserted when remote double-point status input 1 is in the off
RemDPS Ip 1 ON.........................................Asserted when remote double-point status input 1 is in the on
RemDPS Ip 2.................................................The operands listed above are also available for remote
Teleprotection input and output operands
TELEPRO CH1 CRC FAIL...........................Asserted when the CRC detects packet corruption on
TELEPRO CH1 FAIL.....................................Asserted when teleprotection inputs are not received for more
TELEPRO CH1 FAIL OFF ...........................Asserted when teleprotection has failed for channel 1.
TELEPRO CH1 PKT LOST..........................Asserted when the CRC detects a lost packet on teleprotection
TELEPRO CH2 CRC FAIL...........................Asserted when the CRC detects packet corruption on
TELEPRO CH2 FAIL.....................................Asserted when teleprotection inputs are not received for more
TELEPRO CH2 FAIL OFF ...........................Asserted when teleprotection has failed for channel 2.
TELEPRO CH2 PKT LOST..........................Asserted when the CRC detects a lost packet on teleprotection
intermediate state.
(open) state.
(closed) state.
double-point status inputs 2 through 16.
teleprotection channel 1.
than 4 cycles on channel 1.
channel 1.
teleprotection channel 2.
than 4 cycles on channel 2.
channel 2.
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 6: COMMUNICATIONS

Advertisement

Table of Contents
loading