CHAPTER 10: DIGITAL FAULT RECORDER
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 442: Trigger and re-trigger sequence
The length of a transient record is also user-configurable. The number of transient records
Plus
stored by the D90
is a function of the record length, the time-resolution of the recording,
and of the number of configured channels. The D90
number of transient records based on the user-defined setting values.
The transient recorder has two storage modes: protected and automatic overwrite. When
the memory is filled, either no new records are written to memory (protected mode) or the
oldest record is overwritten (automatic overwrite mode).
Plus
The D90
contains a finite amount of memory for record storage. The following table
shows how the transient recorder configuration affects the number of available records.
Table 39: Transient records stored by the D90
Records
8
24
48
8
24
48
20
64
24
64
41
64
Plus
Plus
(examples)
Sampling rate
Digital
channels
256 samples/cycle
128
256 samples/cycle
128
256 samples/cycle
128
128 samples/cycle
128
128 samples/cycle
128
128 samples/cycle
128
64 samples/cycle
128
64 samples/cycle
128
32 samples/cycle
64
32 samples/cycle
64
16 samples/cycle
64
16 samples/cycle
64
TRANSIENT RECORDER
automatically calculates the
Analog
Record
channels
length
16
57
16
22
16
11
16
104
16
40
16
20
16
80
16
26
8
135
8
53
8
124
8
81
497