Direct Devices Status; Iec 61850 Goose Integers; Egd Protocol Status - GE M60 Instruction Manual

Motor protection system ur series
Hide thumbs Also See for M60:
Table of Contents

Advertisement

6 ACTUAL VALUES
The
AVERAGE MSG RETURN TIME
ring configuration (this value is not applicable for non-ring configurations). This is a rolling average calculated for the last
ten messages. There are two return times for dual-channel communications modules.
The
UNRETURNED MSG COUNT
make the trip around the communications ring. The
direct output messages that have been received but fail the CRC check. High values for either of these counts may indicate
on a problem with wiring, the communication channel, or one or more relays. The
values can be cleared using the
COUNT
The
to
DIRECT INPUT 1
DIRECT INPUT (32)
PATH: ACTUAL VALUES
STATUS
 DIRECT DEVICES
 STATUS
MESSAGE
MESSAGE
These actual values represent the state of direct devices 1 through 16.

PATH: ACTUAL VALUES
STATUS
 IEC 61850
 GOOSE UINTEGERS
MESSAGE
MESSAGE
The M60 Motor Protection System is provided with optional IEC 61850 communications capability. This
feature is specified as a software option at the time of ordering. Refer to the Ordering section of chapter 2
for additional details. The IEC 61850 protocol features are not available if CPU type E is ordered.
The IEC 61850 GGIO5 integer input data points are displayed in this menu. The GGIO5 integer data values are received
via IEC 61850 GOOSE messages sent from other devices.
a) FAST EXCHANGE
PATH: ACTUAL VALUES
STATUS
 FAST EXCHANGE 1
MESSAGE
GE Multilin
is the time taken for direct output messages to return to the sender in a direct input/output
values (one per communications channel) count the direct output messages that do not
CRC FAIL COUNT
CLEAR DIRECT I/O COUNTERS
values represent the state of each direct input.


DIRECT DEVICES STATUS

DIRECT DEVICE 1
STATUS: Offline
DIRECT DEVICE 2
STATUS: Offline
DIRECT DEVICE 16
STATUS: Offline

IEC 61850 GOOSE UINTEGERS
UINT INPUT
1
0
UINT INPUT
2
0
UINT INPUT 16
0


EGD PROTOCOL STATUS

FAST EXCHANGE 1
SIGNATURE:
0
FAST EXCHANGE 1
DATA LENGTH:
0
M60 Motor Protection System
values (one per communications channel) count the
UNRETURNED MSG COUNT
command.
6.2.15 DIRECT DEVICES STATUS
Range: Offline, Online
Range: Offline, Online
Range: Offline, Online

6.2.16 IEC 61850 GOOSE INTEGERS

6.2.17 EGD PROTOCOL STATUS
PRODUCER STATUS
FAST EXCHANGE 1
6.2 STATUS
and
CRC FAIL
6
6-9