CHAPTER 10: DIGITAL FAULT RECORDER

Disturbance recorder settings

PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 453: Disturbance recorder screen
Select the Settings > DFR > Disturbance Record menu item to open the disturbance
recorder function configuration window.
Figure 454: Disturbance recorder function settings
The following settings are available.
Function
Range: Enabled, Disabled
Default: Disabled
This setting enables and disables the disturbance recorder function.
Number of Records
Range: 1 to 64 in steps of 1
Default: 48
This setting specifies the total number of disturbance records that can be stored in the
Plus
D90
. A larger setting results in a shorter record length, and vice-versa.
Trigger Mode
Range: Automatic Overwrite, Protected
Default: Automatic Overwrite
If this setting value is "Automatic Overwrite", then the oldest disturbance record will be
overwritten once the number of stored records reaches the setting value. If this value is
"Protected", then no new disturbance record are stored once the number of records
reaches the setting value.
DISTURBANCE RECORDER
507