Sntp Protocol; Security - GE 850 Instruction Manual

Feeder protection system
Hide thumbs Also See for 850:
Table of Contents

Advertisement

DEVICE
IRIG-B
FASTPATH:

SNTP Protocol

NOTE:
NOTE
FASTPATH:

Security

5–8
IRIG-B is available in all 8 Series relays. A failure on IRIG-B triggers an event and a target
message.
Note that IRIG-B is auto detected. The signal type is detected in the hardware, so there are
no configurable options.
850 Feeder Protection System relays accept time synchronization from up to two different
SNTP servers. In order to define number of SNTP servers to be used, different settings for
each SNTP server must be configured.
If one SNTP server is used to synchronize the relay, the SNTP Server and UDP port
settings must be configured with the corresponding settings.
If two SNTP servers are used to synchronize the relay, the SNTP Server IP and UDP port
for the main server must be configured, along with the SNP Server 2 IP and UDP port
for the back-up server.
850 Feeder Protection System relays only support SNTP unicast.
It may take 2-3 minutes for the relay to synchronize with the SNTP server.
Path:
Setpoints > Device > Real Time Clock > SNTP
SNTP FUNCTION
Range: Disabled, Enabled
Default: Disabled
SNTP SERVER IP ADDRESS
Range: Standard IP Address Format
Default: 0.0.0.0
SNTP UDP PORT NUMBER
Range: 0 to 65535 in steps of 1
Default: 123
SNTP SERVER 2 IP ADDRESS
Range: Standard IP Address Format
Default: 0.0.0.0
SNTP 2 UDP PORT NUMBER
Range: 0 to 65535 in steps of 1
Default: 123
The SNTP and PTP settings take effect after rebooting the relay.
The following security features are available:
Basic Security – The basic security feature present in the default offering of the
product.
CyberSentry – The feature refers to the advanced security options available as a
software option. When this option is purchased, it is automatically enabled and Basic
Security is disabled.
GENERAL RULES FOR ROLES
All the roles are password protected, except for the Observer role which is user-
defined on the device. A user with Observer capability defined on the Radius is
password protected.
CHAPTER 5: DEVICE, SYSTEM, INPUT AND OUTPUT SETPOINTS
850 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL