Environmental Specifications; Approvals And Certification - GE D90 Plus Instruction Manual

Line distance protection system
Hide thumbs Also See for D90 Plus:
Table of Contents

Advertisement

CHAPTER 2: PRODUCT DESCRIPTION

Environmental specifications

Approvals and certification

PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
TYPE TESTS
Vibration:.................................................................IEC 60255-21-1, 1G (class Bm)
Shock / bump: ......................................................IEC 60255-21-2, 10G (class Bm)
Seismic (single axis): ..........................................IEC60255-21-3, 1G / 3.5 mm (class 1)
Make and carry (30 A):......................................IEEE C37.90
Conducted immunity: .......................................IEC 61000-4-6 / IEC60255-22-6, class 3 (10 V RMS)
Surge: .......................................................................IEC 61000-4-5 or IEC 60225-22-5, 1.2/50 test up to level 4
Burst disturbance (1 MHz oscillatory):.......IEC60255-22-1 up to 2.5 kV at 1 MHz damped
Fast transients: ....................................................ANSI/IEEE C37.90.1, EC61000-4-4 class 4, (2 kV, 5 kHz / 4 kV,
Radiated immunity: ...........................................IEC 61000-4-3 / IEC 60255-22-3 class 3 (10 V/m) or IEEE
Power frequency disturbance: .....................IEC 61000-4-8 (30 A/m) class 4
Radiated/conducted emissions:..................IEC 60255-25 / CISPR 11/22 class A
Insulation resistance: ........................................IEC 60255-5
Dielectric strength: .............................................IEC 60255-5, ANSI/IEEE C37.90
Dielectric across relay contacts:..................IEEE C37.90 (1.6 kV)
Electrostatic discharge: ...................................EN 61000-4-2, IEC60255-22-2 8 kV C, 15 kV A, L4
Voltage dips/interruptions/variations:......IEC 61000-4-11 (30% 1 cycle), IEC 60255-11
AC ripple:.................................................................IEC 61000-4-17 (standard)
Interruptions on DC power:............................IEC61000-4-29
Damped magnetic immunity:.......................IEC61000-4-10 (level 5, 100A/m)
Impulse voltage withstand:............................EN/IEC60255-5 (5 kV)
Humidity cyclic:....................................................IEC60068-2-30, 6 days 55°C, 95%RH (variant 2)
OPERATING TEMPERATURE
Cold: ..........................................................................IEC 60028-2-1, 16 hours at –40°C
Dry heat:..................................................................IEC 60028-2-2, 16 hours at 85°C
OTHER ENVIRONMENTAL SPECIFICATIONS
Altitude:....................................................................up to 2000 m
Installation category: ........................................II
IP rating: ..................................................................IP30
Noise:........................................................................Negligible
APPROVALS
UL508 17th edition and C22.2 No.14-05: UL listed for the USA and Canada
CERTIFICATION
CE LVD 2006/95/EC:...........................................EN/IEC 61010-1:2001 / EN60255-5:2000
CE EMC 89/336/EEC:..........................................EN 60255-26:2004-08
(4 kV)
2.5 kHz, 2 kV on data control ports and inputs/outputs), IEC
60255-22-4
C37.90.2 radiated RFI (35 V/m)
SPECIFICATIONS
45

Advertisement

Table of Contents
loading

Table of Contents