CHAPTER 8: AUTOMATION

Virtual analog outputs

Shared operands

PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
Figure 399: Trip seal-in scheme settings
There are 128 virtual analog outputs that may be assigned via automation logic. Virtual
analog outputs are resolved in each pass through the evaluation of the automation logic
equations.
Select the Settings > Automation > Automation Inputs/Outputs > Virtual Analogs menu
item to access the virtual analog output configuration settings.
Figure 400: Virtual analog output configuration settings
The settings for virtual analog output 1 are shown below. The settings are identical for all
virtual analog outputs.
Virtual Analog 1 Name
Range: up to 12 alphanumeric characters
Default: Analog 1
This setting specifies an identifier for virtual analog output 1. This value will be included
in the actual values and will also be used to reference output to features designed to
measure this of parameter.
Plus
The EnerVista UR
Setup software groups the D90
primary functions. Each function has its own setting parameters and each generates its
own outputs in the form of operands.
Communications.
Protection.
Automation.
AUTOMATION INPUTS AND OUTPUTS
Plus
system into the following seven
457