GE D90 Plus Instruction Manual page 560

Line distance protection system
Hide thumbs Also See for D90 Plus:
Table of Contents

Advertisement

ANNUNCIATOR PANEL
550
Figure 495: Annunciator configuration page
The following settings are available to configure the annunciator. The settings descriptions
apply to all 288 alarms, with different default values.
Clear Latched
Range: any FlexLogic™ operand or shared operand
Default: OFF
This setting allows the user to designate a FlexLogic™ operand to clear all the latched
alarms when the operand transitions to an active state. For example, a central station
HMI can simultaneously clear all IED alarms remotely by assigning this value to a virtual
input.
Page Layout
Range: 3 × 4, 4 × 6, 6 × 8
Default: 3 × 4
This setting specifies the number of alarms shown per page. This setting applies globally
to all alarm pages. For example if "4 × 6" is selected, then 288 alarms can be displayed
on 12 pages. Note that annunciator pages that do not contain at least one configured
alarm are automatically hidden.
Content
Range: Actual, Alarm, Mixed
Default: Alarm
This setting specifies if the corresponding alarm consists of a single metered value (set
to "Actual"), contains a single alarm indication (set to "Alarm"), or contains both a
metered value and an alarm indication (set to "Mixed").
For details on configuring the alarm when
metering values
on page 552.
Alarm Input
Range: any FlexLogic™ operand or shared operand
Default: see above
This setting specifies the input signal connected to the alarm.
is set to "Actual", see
Content
PLUS
D90
LINE DISTANCE PROTECTION SYSTEM – INSTRUCTION MANUAL
CHAPTER 12: LOCAL INTERFACE
Configuring

Advertisement

Table of Contents
loading

Table of Contents