Data Shifting
Flags
Example
00005
00006
00007
00008
00009
126
tion, the status to be put into the register, the shift pulse, and the reset input.
The control word is allocated as follows:
15 14 13 12
The data in the shift register will be shifted one bit in the direction indicated
by bit 12, shifting one bit out to CY and the status of bit 13 into the other end
whenever SFTR(84) is executed with an ON execution condition as long as
the reset bit is OFF and as long as bit 14 is ON. If SFTR(84) is executed with
an OFF execution condition or if SFTR(84) is executed with bit 14 OFF, the
shift register will remain unchanged. If SFTR(84) is executed with an ON
execution condition and the reset bit (bit 15) is OFF, the entire shift register
and CY will be set to zero.
ER:
St and E are not in the same data area or ST is greater than E.
Indirectly addressed DM word is non-existent. (Content of *DM word
is not BCD, or the DM area boundary has been exceeded.)
CY:
Receives the status of bit 00 of St or bit 15 of E, depending on the
shift direction.
In the following example, IR 00005, IR 00006, IR 00007, and IR 00008 are
used to control the bits of C used in @SHIFT(84). The shift register is be-
tween LR 20 and LR 21, and it is controlled through IR 00009.
05012
Direction
05013
Status to input
Shift pulse
05014
05015
Reset
@SFTR(84)
050
LR 20
LR 21
Not used.
Shift direction
1 (ON):
Left (LSB to MSB)
0 (OFF): Right (MSB to LSB)
Status to input into register
Shift pulse bit
Reset
Address Instruction
00000
LD
00001
OUT
00002
LD
00003
OUT
00004
LD
00005
OUT
00006
LD
00007
OUT
00008
LD
00009
@SFT(10)
LR
LR
Section 5-13
Operands
00005
05012
00006
05013
00007
00514
00008
05015
00009
050
20
21