Installation And Control Panel Wiring (B308) - Bosch B6512 Installation Manual

Hide thumbs Also See for B6512:
Table of Contents

Advertisement

Control Panels
11.1.3

Installation and control panel wiring (B308)

Ensure that there is enough power for the module and other powered devices you want
connected to the system.
Refer to On-board outputs, page 50.
Caution!
Remove all power (AC and battery) before making any connections. Failure to do so might
!
result in personal injury and/or equipment damage.
Install the module
1.
2.
3.
Wire to the control panel
When you wire an SDI2 module to a control panel, you can use either the terminal strip
labeled with PWR, A, B, and COM to wire to corresponding SDI2 terminals labeled on the
control panel, or you can use the interconnect wiring connector and the included interconnect
cable.
For terminal wiring, use 18 AWG to 22 AWG (1.02 mm to 0.65 mm) wire.
Notice!
Use either the terminal strip wiring or interconnect wiring to the control panel. Do not use
both. When connecting multiple modules, you can combine terminal strip and interconnect
wiring connectors in series.
1
Figure 11.1: B308 to control panel wiring - terminal strip or interconnect wiring connector
Callout ᅳ Description
1 ᅳ Control panel
2 ᅳ Module
3 ᅳ Terminal strip wiring
4 ᅳ Interconnect cable (P/N: F01U079745) (included)
Bosch Security Systems, Inc.
Set the module address using the address switches before you install it in the enclosure.
Install the module in the enclosure with the control panel or in an adjacent enclosure that
is within the distances rated for the module: 400 ft (137 m) with 22 AWG (0.65 mm) wire
or 1000 ft (305 m) with 18 AWG (1.02 mm) wire.
Use the screws provided with the module to secure the module in the enclosure.
SDI2
ON-BOARD POINTS
Device Bus
Voltage Ranges
R Y G B
Open
3.7 - 5.0 VDC
Normal
2.0 - 3.0 VDC
Short
0.0 - 1.3 VDC
1 k
End of Line Resistors
AUX
1 COM 2
3 COM 4 5 COM 6
- 12 V +
COM AUX
R
Y
G
B
1
COM
2
3
COM
4
5
COM
PWR A
B COM
R Y G B
2
3
C
OUTPUT
B
7 COM 8
6
7
COM
8
2
PWR A B COM
PWR A B COM
Installation Manual
Off-board outputs | en
SDI2
ON-BOARD POINTS
1
Device Bus
Voltage Ranges
R Y G B
Open
3.7 - 5.0 VDC
Normal
2.0 - 3.0 VDC
Short
0.0 - 1.3 VDC
1 k
End of Line Resistors
AUX
1 COM 2
3 COM 4 5 COM 6
- 12 V +
COM AUX
R
Y
G
B
1
COM
2
3
COM
4
5
COM
PWR A
B COM
4
2017.04 | 15 | F.01U.287.180
53
C
OUTPUT
B
7 COM 8
6
7
COM
8