Enclosures - Bosch B6512 Installation Manual

Hide thumbs Also See for B6512:
Table of Contents

Advertisement

86
en | Approved applications
The Reset Sensor command is available from the keypads when the Reset Sensor is enabled.
Connect the smoke detectors to a suitable interface such as the B208 Octo-input Module or
on-board point to meet UL and NFPA requirements.
Notification Appliance Circuit (NAC)
Refer to Notification appliance circuit wiring, page 76.
Notice!
Test Weekly: Perform a Fire Test weekly.
Further information
NFPA Style A (Class "B") Circuit
Loops A and B on the D125B Module are NFPA Style A (Class "B") initiating circuits suitable
for connecting any fire alarm initiating device, including two-wire and four-wire smoke
detectors.
Connecting initiating devices to on-board points (1 through 8) on the control panel.
Connecting initiating devices to off-board points:
Other devices
Use a D130 Relay Module, D8129 OctoRelay, or Switched Aux (Terminal 8) to provide reset
capability to other initiating devices such as:
Install devices according to the manufacturer's instructions. For more information, refer to Off-
board outputs, page 52.
For battery calculations, refer to Standby battery requirements and calculations, page 89.
Notice!
Test Weekly: Perform a Fire Test weekly. According to UL 864, a Fire Test tests both the AC
power and the battery.
19.1.4

Enclosures

Mount the control panel assembly in any of the Bosch Security Systems, Inc. enclosures listed:
2017.04 | 15 | F.01U.287.180
Household Fire Warning equipment, page 91
Use a D125B Powered Loop Interface Module with two-wire initiating devices.
Use a D129 Dual Class "A" (NFPA Style D) Initiating Circuit Module with any type of
initiating device, except a two-wire smoke detector.
Do not connect two-wire smoke detectors to POPITs or MUX bus inputs.
Use the D9127U or D9127T POPIT Modules to connect four-wire smoke.
B308 Octo-output Module
D125B Powered Loop Interface Module (2-wire smoke detector module)
D129 Dual "Class A" Initiation Circuit Module (4-wire smoke detector)
D9127T/U POPITs
On-board points
B10 Medium Control Panel Enclosure
B11 Small Control Panel Enclosure
D2203 Enclosure
B8103 Universal Enclosure*/D8103 Universal Enclosure*
D8109 Fire Enclosure (red)*
D8108A Attack Resistant Enclosure*
Installation Manual
Control Panels
Bosch Security Systems, Inc.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

B5512B4512B3512B5512eB4512eB3512e

Table of Contents