C)
Air Filters
D)
Air filters can be obtained in bulk quantities from Toshiba International Corporation. Use only air filters
specified by Toshiba.
UNIT
1000 kVA
5 ea. 15"x30"x1" , Arrestance: 60-80%, Eff. <20%, MERV 1-4
8
FAULT CODES
This section covers fault codes, their description and required action.
In the event of a fault occurring:
A) Verify and record the occurrence of the alarm. Note details of alarm message displayed on the LCD
display panel.
Contact Toshiba International Corporation at 1-877-867-8773
B) If a circuit breaker (MCCB) has tripped, depress the toggle to reset the breaker before closing it
again.
8.1
BYPASS MODULE FAULT CODES
Code
Status
indication
Message
(Note 2)
UA805
OVERLOAD
INVERTER
UA806
OVERLOAD
INVERTER
UA807
OVERLOAD
UA808
OVERLOAD
UA810
OVERLOAD
48
Table 7-2 Ait Filters
Toshiba Part Number
T90-AF-15x30x1
Table 8-1 Bypass Module Fault Code List
BYPASS MODULE FAULT CODE LIST
Meaning
The output load current has
exceeded 100% of the rated
current.
The output load current peak has
exceeded 220% of the rated
current.
The output load current has
exceeded 105% of the rated
current.
The output load current has
exceeded 100% of the rated
current during bypass supply.
Short time over-current has
exceeded 150% of the rated
current.
G9000 Installation and Operation Manual – 61480-012
Quantity (per unit)
5
Audible
Guidance
Alarm
WARNING:
Intermittent
DECREASE
sound
LOAD
WARNING:
Intermittent
DECREASE
sound
LOAD
WARNING:
Intermittent
DECREASE
sound
LOAD
WARNING:
Intermittent
DECREASE
sound
LOAD
WARNING:
Intermittent
DECREASE
sound
LOAD
External
relay
contact
(Note 1)
Overload
Overload
Overload
Overload
Overload