Table 5-4 Recommended Cable Sizes; Table 5-5 Recommended Hardware - Toshiba G9000 SERIES Installation And Operation Manual

480/480 v 1000kva
Hide thumbs Also See for G9000 SERIES:
Table of Contents

Advertisement

kVA
Input
Output
Capacity
Voltage
Voltage
1000kVA
480V
480V
*1 – Use 75 degree C copper wire.
*2 - The cables must be selected to be equal or larger to the sizes listed in the table.
*3 - Voltage drop across power cables not to exceed 2% of nominal source voltage.
*4 - Allowable ampere-capacities based on copper conductors with 75 degree C. insulation at ambient temperature of 40 degree C.

Table 5-5 Recommended Hardware

UPS Capacity
Bolt size
1000kVA
M12 x 40mm
34

Table 5-4 Recommended Cable Sizes

Input Side
Cable
Torque
Size
in. lbs
5 x 400MCM or
347 - 469
5 x 400MCM or
6 x 300MCM
in. lbs
6 x 300MCM
Flat washer
Split lockwasher
size
size
M12
M12
G9000 Installation and Operation Manual – 61480-012
Output Side
Cable
Torque
Cable
Size
in. lbs
Size
347 - 469
5 x 400MCM or
in. lbs
6 x 300MCM
Nut size
M12
Bypass Side
DC Input Side
Torque
Cable
in. lbs
Size
347 - 469
8 x 500MCM or
in. lbs
10 x 350MCM
Torque
in. lbs
347 - 469
in. lbs