Toshiba G9000 SERIES Installation And Operation Manual page 64

480/480 v 1000kva
Hide thumbs Also See for G9000 SERIES:
Table of Contents

Advertisement

Code
indication
(Note 2)
MF253
CTRL.CIRCUIT ERR.
MF254
COOLING FAN ABNL.
MF256
O/P VOLTAGE ABNL.
MF301
CTRL.CIRCUIT ERR.
MF302
CTRL.CIRCUIT ERR.
MF303
CTRL.CIRCUIT ERR.
MF305
CTRL.CIRCUIT ERR.
MF306
CTRL.CIRCUIT ERR.
MF309
INV.VOLTAGE ABNL.
MF320
CTRL.CIRCUIT ERR.
MF331
CTRL.CIRCUIT ERR.
MF332
CTRL.CIRCUIT ERR.
MF333
CTRL.CIRCUIT ERR.
MF334
CTRL.CIRCUIT ERR.
MF376
CTRL.CIRCUIT ERR.
MF552
DUMMY FAULT
(Note 1) 1) "Major" is defined as a major failure. Load transferred from the inverter circuit to the static
bypass line;
2) "Minor" is defined as a minor failure. UPS continues to operate normally, but the cause of
alarm must be identified;
(Note 2) Code indication means:
#A+++ --------------------- Alarm
#F+++ ---------------------- Failure
#%0++ --------------------- Rectifier circuit failure
#%1++ --------------------- DC circuit failure
#%2++ --------------------- Inverter circuit failure
#%3++ --------------------- Control circuit failure
#%4++ --------------------- Bypass system failure
#%8++ --------------------- Alarm
"#" Bypass Module "U", UPS Module "M"
"+" denotes any numeral from 0 to 9
"%" denotes either "A" or "F"
54
UPS MODULE FAULTS CODE LIST
Status
message
Discrepancy between output voltage and inverter
voltage, or between output voltage and bypass
voltage.
Thermal relay of cooling fan worked.
Output voltage is out of the specified range.
AD reference has an abnormal value.
Detection of an external interruption during the
software execution.
Timer does not reset in the specified period (WDT
settings)
Detection of an abnormal clock speed in the DSP or
FPGA.
Control power supply voltage is below the specified
level.
Inverter voltage is out of the specified range.
Cable disconnection in the parallel interface board
during load supply.
Cable disconnection in the main driver PCB (Phase A)
Cable disconnection in the main driver PCB (Phase B)
Cable disconnection in the main driver PCB (Phase C)
Cable disconnection in the main driver PCB
(Chopper))
Logic signal abnormal (Supply ON)
Bypass Module send fault simulation signal.
Meaning
G9000 Installation and Operation Manual – 61480-012
External relay
contact
(Note 1)
Minor
Minor
Minor
Major
Major
Major
Major
Major
Major
Major
Major
Major
Major
Major
Minor
Major